For fixing on to, for example, walls or other structures
The maximum free length refers to the distance between the rod tip and the upper holder (fixing point). For reasons of stability, the centre holder (3 fixing points) should be mounted directly below the upper holder if possible. The distance must not be more than 15 cm. The lower holder (fixing point) has to be installed within a range of ≤ 15 cm at the end of the air-termination rod.
Total length (l1) | 4000 mm |
Length of tube (Ø40 x 5) | 2000 mm |
Length of air-termination rod (Ø16 / 10) (l4) | 2000 mm |
Max. free length with air-termination rod (l2) | 3500 mm |
Clamping length (l3) | 500 mm |
Number of fixings | 2 |
Max. gust wind speed | (Wall mounting with a free length of 3,500 mm) 185 km/h |
Material of air-termination rod | Al |
Standard | EN 62561-(1+2) |